Battery Backup Calculator

Find how long your battery will last, or how big a battery bank you need for your home or shop.

Enter your battery bank and load to find out how long it will run.

Not sure of your load? Use our Inverter Load Calculator.

How it is calculated

Backup time (h) = Battery V × Ah × No. of batteries × DoD × Health × Inverter efficiency ÷ Load (W)

Battery size (Ah) = Load (W) × Hours ÷ (Inverter efficiency × DoD × Health × System voltage)

Frequently Asked Questions

How do I calculate battery backup time?+

Backup time (hours) = Battery voltage × Ah × number of batteries × usable DoD × battery health × inverter efficiency ÷ load in watts. For example, two 12V 150Ah tubular batteries on a 500W load give about 2 × 12 × 150 × 0.8 × 0.85 ÷ 500 ≈ 4.9 hours.

What is depth of discharge (DoD)?+

DoD is the share of a battery's rated capacity you can safely use. Tubular lead-acid is typically 80%, flat plate 50%, VRLA/SMF about 60% and lithium (LiFePO4) about 90%. Draining beyond this shortens battery life.

How many batteries do I need for my inverter?+

Use the Battery Size mode: enter your load and the hours of backup you need. The calculator returns the required Ah at the right system voltage (12V, 24V or 48V) and the number of batteries in series and parallel.

Why is my actual backup less than the calculated time?+

Old batteries, high starting current of motors and compressors, hot weather, and inverter losses reduce runtime. Use the battery health option to account for ageing.

Can I add solar to extend backup?+

Yes. A solar hybrid system recharges the battery in the daytime and can extend backup significantly. Talk to our experts for a custom design.